不同规格的燃气锅炉的作用效果不同
    2018-3-2 14:25:24  文章来源:http://www.jnlzsb.com
    (1)锅炉房及燃料贮运建筑的耐火等级和防火要求应符合。
    (1) the fire-proof grade and fire protection requirements of the boiler room and the fuel storage and transportation building should be met.
    (2)锅炉房的外墙或屋顶至少应有相当于锅炉房占地面积10%的泄压面积,如采用玻璃窗、天窗、薄墙等。泄压处不得与聚集人多的房间和通道相邻。
    (2) the external wall or roof of the boiler room should be at least equivalent to 10% of the area of pressure relief for the boiler room, such as glass window, skylight, thin wall and so on. The pressure relief office should not be adjacent to a room and channel with many people gathered.
    (3)锅炉房内的设备布置应留有必要的间距、通道,便于安装、操作、通行和检修。

    (3) the equipment arrangement in the boiler room should have the necessary spacing and channel, which is convenient for installation, operation, passage and maintenance.

    山东燃气锅炉

    (4)锅炉房应有足够的光线(照明)和良好的通风以及必要的降温、防冻措施。操作间尽可能与锅炉及辅机和附属设施分开,减小噪声、油气等对操作人员的伤害。
    (4) the boiler room should have sufficient light (lighting) and good ventilation as well as necessary cooling and anti freezing measures. As far as possible, the operating room can be separated from the boiler and auxiliary equipment and auxiliary facilities to reduce the damage to the operator by noise and oil and gas.
    (5)锅炉房内的地面应平整无台阶,且应防止积水、积油。
    (5) the ground in the boiler room should be flat and without steps, and the water and oil should be prevented.
    (6)锅炉房承重梁柱等构件与锅炉应有一定距离或采取其他措施,以防止受高温损坏,减弱承重强度或缩短使用年限。
    (6) boilers, load-bearing beams, columns and other components should be at a certain distance from the boiler or take other measures to prevent damage to the high temperature, weaken the bearing strength or shorten the service life.
    (7)锅炉房每层至少应有两个出口,分别设在两侧。但锅炉前端的总宽度(包括锅炉之间的过道在内)不超过12m,且面积不超过200m2的单层锅炉房,可以只开一个出口。
    (7) the boiler room should have at least two exits each layer on both sides of the boiler room. But the total width of the front of the boiler (including the aisle between the boilers) is not more than 12M, and the single layer boiler room with an area of no more than 200m2 can only open one outlet.
    (8)锅炉房通向室外的门应向外开,且不宜采用金属卷闸门。在锅炉运行期间不准将门锁住或闩住,锅炉房的出入口和通道应畅通无阻,不得堆放杂物。
    (8) the door to the outside of the boiler room should be opened outward, and the metal gate should not be used. Don't lock the door or bolted in the boiler operation, and exit channel boiler room should be smoothly, no debris piled up.
    您的需求就是我们努力的方向,您的追求就是我们的追求,欢迎您的到来,我们一起进步,一起创新!
    Your demand is the direction of our efforts, your pursuit is our pursuit, welcome your arrival, we progress together, together innovation!