    锅炉的控制系统你了解哪些?
    来源:http://www.jnlzsb.com 发布时间:2020-09-03

    1.压力传感器:锅炉压力通过压力传感器控制。当压力低于压力控制仪设定值时压力控制器输出信号接通;压力高于设定值时信号断开;信号断开后当压力下降到回差设定值时再次接通。(注:产品出厂时已设定好,客户如需另行更改,请联系本公司售后服务工程师。)
    1. Pressure sensor: boiler pressure is controlled by pressure sensor. When the pressure is lower than the set value of the pressure controller, the output signal of the pressure controller is connected; when the pressure is higher than the set value, the signal is disconnected; after the signal is disconnected, it is connected again when the pressure drops to the set value of return difference. (Note: the product has been set before delivery. If you need to change it, please contact our after-sales service engineer.)
    2.压力控制器:锅炉的超压保护由压力控制器检测信号输出,当锅炉运行压力超过额定工作压力时,压力控制器输出信号停止锅炉运行。
    2. Pressure controller: the overpressure protection of the boiler is output by the detection signal of the pressure controller. When the operating pressure of the boiler exceeds the rated working pressure, the pressure controller outputs the signal to stop the operation of the boiler.
    3.水位信号:控制器使用水位电极测量水位,使用时应注意水位电极两端的绝缘,不要受潮。当水位电极两端的电阻低于100K时,控制器认为水面已高于电极;当水位电极两端电阻升500K以上时,控制器即认为水面已低于电极。
    山东电采暖锅炉
    3. Water level signal: the controller uses the water level electrode to measure the water level. When using, pay attention to the insulation at both ends of the water level electrode, and do not get damp. When the resistance at both ends of the water level electrode is lower than 100k, the controller thinks that the water surface is higher than the electrode; when the resistance at both ends of the water level electrode rises above 500K, the controller thinks that the water surface is lower than the electrode.
    4.液位浮球控制(定制功能,订货时请注明):针对于使用纯水或去离子水(导电率非常低而引起水位电极检测水位失灵,我们采用浮球式水位监测。通过液位对浮球开关的触发控制锅炉水位。)
    4. Liquid level floating ball control (customized function, please specify when ordering): for the use of pure water or deionized water (the conductivity is very low, which causes the water level electrode to detect the water level failure, we use the floating ball water level monitoring. The boiler water level is controlled by triggering the float switch by the liquid level.)
    5.远程控制:远程控制可实现本设备的单机运行,或由主机给出开关启动信号实现本设备远程启动,并对运行过程实施过程监控,报警输出提醒。
    5. Remote control: the remote control can realize the single machine operation of the equipment, or the host can give the switch start signal to realize the remote start of the equipment, and implement process monitoring and alarm output reminder during the operation process.
    6.报警保护:控制器开启后即不间断地对压力传感器、水位电极以及自身电路进行检测,发现故障立即报警并停炉保护。控制器自动显示故障点,机内蜂鸣器发出报警声。
    6. Alarm protection: after the controller is turned on, it will continuously detect the pressure sensor, water level electrode and its own circuit, and immediately alarm and shut down the boiler for protection in case of any fault. The controller automatically displays the fault point, and the buzzer in the machine sends out an alarm.
    有了山东电采暖锅炉上面的小总结,希望对广大客户有所帮助,如果有什么不理解的或者寻求帮助的请点击我们的网站:http://www.jnlzsb.com或者来电咨询,我们会尽全力为您